DIGISAVE RD

Directional multi-functional protection

Description
Alttext

The protection relay DIGISAVE RD is primarily used to protect isolated or compensated neutral point lines and transformers in medium voltage networks and for wind power generators and mains tie-point, and also possesses all the functions of a simple busbar protector (reverse interlocking).

DIGISAVE RD possesses a number of functions and features that enable it to respond appropriately to the requirements of our customers' systems and power networks. For example, the fact that connections can be made using a plug-in socket, plus the patented extended wattmetric method for the rapid and reliable detection of earth faults.

Freely parameterisable LEDs and a four-line screen displaying intelligible messages make it possible to clearly and easily convey the status values of the various processes, enabling operators to always be alert to the equipment's current and foregoing states. Protection parameters are set up in the simplest possible way - on the protection relay itself, using a single turn-and-press knob and with menu guidance. Naturally you can also use the operating program DIGICOM to set up the parameters.

DIGISAVE RD meets the high standard expected of "swiss made quality" and fulfils all the homologation tests specified in IEC 60255.

Special features
  • Mechanically and electrically compatible with RN1 protection relays
  • Plug-in socket with integrated current converter short (all signals such as current or voltage converter input and binary inputs and outputs are wired to the plug-in base/test socket)
  • Operated with a single knob (turn and press)
  • 11 parameterisable LEDs
  • Four-line display
  • Not battery buffered
  • 300VDC / 50J triggering capacitors for standard power circuit breaker coils (>50Ω)
  • 48VDC capacitors for secure logic inquiries
  • RS232 parameterisation interface on the front
  • IEC 60870-5-103
  • H2 logic (line-monitored reverse interlocking)
Function overview
Protective functions
  • 2-stage (non)-directional overcurrent time-graded protection (50,51)
  • 2-stage non-directional fault current detection (50N, 50G, 51N, 51G)
  • Directional overcurrent time-lag earth protection (67N)
  • Directional or non-directional sensitive fault current detection (67Ns, 50Ns)
  • Displacement voltage (64)
  • 2-stage overload protection (49)
  • Inrush stabilisation (68)
  • Undercurrent protection (37)
  • Start-up time monitoring (48)
  • Reclosure prevention (66/86)
  • Circuit breaker failure protection (50BF)
  • Unbalanced load protection (46)
  • Automatic reclosure ARC (79)
  • Switch on to fault protection (50SOTF)
  • 2-stage undervoltage and overvoltage protection (27/59)
  • 2-stage underfrequency and overfrequency protection (81O/U)
  • Rotatory field monitoring (47)
  • Lockout (86)
Monitoring functions
  • Operating measurements U, I, f, S, P, Q, cos(phi)
  • Up to 15-minute averages
  • Events (100,000 entries)
  • 6 fault logs COMTRADE V99
    (max. 3000ms each)
  • Extensive self tests and test functions
  • User-defined logic (e.g. locking)
Communication interfaces
  • RS232 system / service interface for DIGICOM
  • IEC 60870 5 103 (electrical; RJ45)
Hardware
  • Compact sheet steel housing
  • Wide-range AC or DC power feed
  • 4 current converters (1A or 5A)
  • 3 voltage converters (100/110VAC)
  • 2 binary inputs (optocouplers)
  • 6 binary outputs (power relays)