DIGISAVE RN

Non-directional multi-functional protection

Description
Alttext

 

The protection relay DIGISAVE RN is used to protect isolated or compensated neutral point lines and transformers in medium voltage networks and also possesses the full functionality of a motor protection.

DIGISAVE RN possesses a number of functions and features that enable it to respond appropriately to the requirements of our customers' systems. For example, the fact that connections can be made using a plug-in socket, plus the comprehensive power management of the protection relay's power feed (power consumption <1VA). In this version the current converter power feed requires only a principal current converter with a power rating of 1VA. This dual-power or triple-power relay can operate with a converter power supply as low as 0,2In at 200mVA per phase.

Freely parameterisable LEDs and a four-line screen displaying intelligible messages make it possible to clearly and easily convey the status values of the various processes, enabling operators to always be alert to the equipment's current and foregoing states. Protection parameters are set up in the simplest possible way - on the protection relay itself, using a single turn-and-press knob and with menu guidance. Naturally you can also use the operating program DIGICOM to set up the parameters.

DIGISAVE RN meets  the high standard expected of "swiss made quality" and fulfils all the homologation tests specified in IEC60255.

Special features

 

  • Mechanically and electrically compatible with RN1 and RN1.2 protection relays
  • Plug-in socket with integrated current transformer short-circuiter (all signals such as converter input, binary inputs and outputs are wired to the plug-in socket)
  • Operated with a single knob (turn and press)
  • 11 parameterisable LEDs
  • Four-line display
  • Mechanical flag indicator
  • No batteries needed
  • 300VDC / 50J triggering capacitors for standard power circuit breaker coils (>50Ω)
  • 48VDC capacitors for secure logic inquiries
  • RS232 parameterisation interface on the front
  • IEC 60870-5-103
Function overview
Protective functions
  • 2-stage non-directional overcurrent time-graded protection (50,51)
  • 2-stage non-directional ground fault protection (50N, 50G, 51N, 51G)
  • 2-stage overload protection (49)
  • Inrush stabilisation (68)
  • Motor protection
  • Undercurrent protection (37)
  • Start-up time protection (48)
  • Reclosure prevention (66/86)
  • Rotor-lock protection (14)
  • Load step protection (51M)
  • Circuit breaker failure protection (50BF)
  • Unbalanced load protection (46)
  • Automatic reclosure ARC (79)
  • Switch on to fault protection (50SOTF)
Monitoring functions
  • Current measurement
  • 15-minute averages
  • Events (100,000 entries)
  • 5 fault logs COMTRADE V99 (max. 2500ms each) 
  • Extensive self tests and test functions
  • User-defined logic (e.g. locking)
Communication interfaces
  • RS232 system / service interface for DIGICOM
  • IEC 60870 5 103 (electrical; RJ45)
Hardware
  • Compact sheet steel housing
  • Wide-range AC or DC power feed
  • 4 current converters (1A or 5A)
  • 2 binary inputs (optocouplers)
  • 6 binary outputs (power relays)